Mini and Maxi Verticus

MINI VERTICUS and MAXI VERTICUS combine compressor, air purification, SECURUS electronic moisture monitoring system and motor in a space saving, sound attenuated vertical cabinet designed to diminish operating sound levels. The MINI VERTICUS sound level is approximately 70 dBA and the MAXI VERTICUS is less than approximately 79 dBA (both at 3ft/ 1meter distance).

STANDARD SCOPE OF SUPPLY

  • BAUER Breathing Air Purification System with SECURUS
  • BAUER PLC based controller with
    multicolor touchpad display
  • NEMA 4 rated electrical enclosure
    with UL® listed control panel
  • Compressor low oil pressure and
    high temperature safety shutdowns
  • Emergency stop push bottom automatic start/stop control
  • Automatic condensate drain system with non-corrosive
    condensate reservoir and integrated float sensor.
    Automatic "Full" indication and compressor shutdown

Maxi Verticus Models (add to above)

  • Vertically hinged front operations panel
    and lift-off side maintenance access doors
  • Inlet filter maintenance indicator
  • Interstage pressure guages (locally mounted)

AVAILABLE ACCESSORIES (factory installed)

Mini Verticus Models

  • Audible alarms for safety shutdowns
  • CO monitor
  • Interstage pressure gauges (locally mounted

Maxi Verticus Models

  • Audible alarms for safety shutdowns
  • CO monitor with remote display

DIMENSIONS L x W x H inches (mm)

  • MINI VERTICUS 29 x 49 x 58 (737 x 1245 x 1473)
  • MAXI VERTICUS 51 x 34 x 66 (1295 x 864 x 1676) (15-20hp)
  • MAXI VERTICUS 68 x 45 x 75 (1727 x 1143 x 1905) (30hp)

WEIGHT pounds (kg)

  • MINI VERTICUS 880 - 950 (400 - 432)
  • MAXI VERTICUS 1050 - 1530 (476 - 694)

Technical Data

Model Charging
Rate*
Number
of
Stages
Motor FAD** RPM Purification
System
  scfm I/min   hp kW      
5000 psig (345 bar)
mVT6-E1/E3 6 170 3 5 3.7 5 1050 P2 SECURUS
mVT8-E1/E3 8.4 238 3 7.5 5.6 7 1250 P2 SECURUS
MVT20-E3 21 595 4 15 11 17.5 1300 P5 SECURUS
MVT26-E3 26.4 748 4 20 15 22 1350 P5 SECURUS
MVT42-E3*** 42 1190 4 30 22 35 2300 P10 SECURUS
6000 psig (414 bar)
mVT5H-E1/E3 5 142 3 5 3.7 4 1050 P2 SECURUS
mVT10H-E1/E3 9.7 275 4 7.5 5.6 8.1 1180 P2 SECURUS
mVT13H-E1/E3 13 368 4 10 7.5 10.8 1420 P2 SECURUS
MVT18H-E3 18 510 4 15 11 15 1325 P5 SECURUS
MVT25H-E3 25.2 714 5 20 15 21 1300 P5 SECURUS
MVT35H-E3*** 35.9 1017 4 30 22 29.8 1200 P10 SECURUS

*Based on recharging an 80 cubic foot tank from 500 to 3000 PSIG.
**Compressor capacity referenced to standard inlet conditions.
***30 Hp units are in a cabinet other than depicted.
E1 = Single phase electric, 230 VAC/60 Hz. E3 = Three Phase Electric, 230/460 VAC/60 Hz
mVT = MINI VERTICUS MVT = MAXI VERTICUS
Dimensions and weights are approximate and are subject to change.