Home > SNGII Sequence of operation
SNGII Sequence of operation
1328 Azalea Garden Rd.
Norfolk VA. 23502
757-855-6006
Fax: 757-855-3761
Date: November 2003
Contact: Product Support ( )
Contents
Scope
Sequence Of Operation
Interface Screens
Main Screen
System Values
System inputs
System Outputs
Output Test
Edit Setpoints
Shutdown/Restart Pressure
Set Oxygen Limits
ACD settings
Overrun and Membrane inlet tempurature Fault
Set System Clock
Maintenance Screen
Last five system Faults
Stack Lights
Message Center
Fault Codes
Scope
This bulletin describes the general sequence of operation and user interface for the model SNGII Stationary Nitrogen Generators incorporating the BK15.3 high pressure booster with variable inlet pressure. Utilizing a variable inlet pressure booster, the SNGII minimizes generator warm up times by initiating product production under low capacity conditions. This means that product will flow within minutes from the system within the user adjustable purity limits. As the membrane bundle in the center of the system continues to warm, allowing reduced Oxygen content, the SNGII control system automatically ramps up the inlet pressure to the high pressure booster to provide the maximum system capacity at the preset purity setpoints.
Sequence of operation
Upon pressing the start button, SNGII control system will measure the current system outlet pressure. If the outlet pressure is below the preset restart pressure, the low pressure compressor contactor will be energized and the low pressure screw compressor will then begin to rotate and pressurize the membrane bundle. Prior to passing through the membrane bundle, the air will pass through the screw compressor aftercooler and a filter bank, then back through a shell and tube heater exchanger flooded with the hot oil from the low pressure compressor. This will assure a particulate free gas below dew point to the membrane bundle for maximum efficiency.
While the gas is passing through the membrane bundle, the Oxygen in the air stream passes through the membrane fibers allowing for a nitrogen enriched gas stream to be passed on to the high pressure booster system. The control system will monitor the inlet pressure to the booster and upon reaching a pressure greater than 75 psig, the booster motor contactor will be energized and the booster will rotate. The booster inlet pressure will then be ramped up to 99 psig and the automatic condensate drain and high pressure vent valve will be opened in order to purge the booster system. During this time, the onboard Oxygen monitor will measure the oxygen content of the gas being supplied to the high pressure system. Once the Oxygen content drops below the preset upper Oxygen limit, the high pressure vent valve will be closed and the system will begin to pump product down stream.
As the membrane bundle begins to warm up, its ability to separate out the Oxygen in the gas stream improves and the Oxygen content in the gas being supplied to the booster begins to decrease further. Once the purity drops below the lower preset Oxygen limit, the control system will slowly increase the booster inlet pressure. This increase in inlet pressure will provide for an increase in booster capacity, and with the increase in gas flow from the membrane bundle, the separation efficiency will decrease, increasing the Oxygen content of the product flow until in is once again between the upper and lower preset Oxygen limits. This process will repeat itself until the system is supplying the maximum capacity for the O2 limits entered. If the preset O2 limits are such that the booster inlet is increased to its maximum, any further increase in membrane temperature will have the effect of supplying a higher quality gas than required.
While the system continues to pump, the control system will periodically drain any accumulated liquids in the high pressure booster using the Automatic Condensate Drain (ACD) and will monitor the systems fault inputs. It should be noted that during an ACD event, the surge in gas through the booster may cause the gas purity to briefly exceed the preset limits. At this time the control system will automatically purge the booster block by opening the high pressure vent valve and decreasing the booster inlet pressure. This will quickly pull the purity back within limits at which point the pumping of product will continue.
Once the outlet system has been pressurized to the preset system shutdown pressure, the SNGII will shut down the booster and the low pressure system until the outlet pressure falls below the preset restart pressure setpoint.
User Interface Screens
Main Screen:When power is applied to the SNGII unit, and the E-Stop switch pulled out, the on board touch screen display will illuminate and display the Main screen. The main screen will display the current outlet pressure, the current system time, and the current system status, in addition to the main start and stop push buttons for the unit. When power is cycled to the unit, its default status will be "System Off". |
System Values:Pressing the System Values button on the main screen will display the current system values screen. This screen will display the system status (from main screen) at the top and then list the current system values being read by the PLC as follows. |
System Inputs:The inputs screen displays the current status of the system switches as follows: |
System Outputs:The system outputs screen displays the status of the individual system loads: |
System Output Test:The system outputs screen displays the status of the individual system loads and provides test buttons next to each load indicator. Pressing the test button next to the load will energize the output on the PLC to which the load is attached. The load is energized for the period the button is depressed and automatically de-energizes when the button is release. Note: this page only available when the system is placed in the Off Mode (stop button on main screen pressed). If the load does not function when the respective test button is depressed, but the indicator light illuminates indicating that the PLC thinks the load is powered, then the problem at hand would be a physical wiring or defective load issue. If the indicator light does not illuminate when the test button is depressed, then the PLC operation has been halted or a PLC error has occurred. |
System SetpointsThe system setpoints screen gives the operator access to the main system parameters. The adjustable system parameters are: |
Shutdown /Restart PressureTouching the values in the shutdown and startup boxes will open a keypad to allow these values to be changed. One should note that the following rules apply: |
Oxygen LimitsThe Oxygen limits setpoints are responsible for the way the control system adjusts the inlet pressure to the booster. After the unit has started, the membrane pressurized and the booster started at a minimum inlet pressure (99 psig), the control system will not close the high pressure vent valve and produce product until the O2 content has dropped below the upper limit. |
ACD TimersDuring operation, the booster block compresses and cools the gas product. It will be possible during this process that liquid water and oil will be condensed into liquid form which must be removed. The booster block uses interstage and outlet separators to collect these liquids and an automatic condensate drain device to purge them from the system. The default value for the interval between drain events is its maximum of 50 minutes. This value can be reduced for testing purposes however surges in gas flow during drain events may cause purity spikes resulting in additional block purging. The drain period sets the time the automatic condensate drain is open during each drain event and should be set between 4 to 6 seconds. |
Overrun and Membrane inlet temperature:The Overrun timer sets the maximum period the unit will be allowed to operate without reaching the final pressure shutdown setting. This fault is design to prevent the unit from running continuously in the event the downstream piping system develops leaks that are greater that the systems capacity. The default setting is 8 hours and can be set as high as 24 hours. |
Set ClockThe PLC contains a running clock that is used to time stamp system events. Pressing the set clock button on the main screen will open this screen and allow the systems calendar and clock to be edited. The date and time information will be displayed along with the last five system faults in the System faults screen, accessible from the System values screen. The date and time stamp information will also be used to stamp the last five system run times that are accessible through the external BC_LINK interface software. |
System MaintenanceAvailable by pressing the "Maintenance " button on the System Values screen, the maintenance screen will display the amount of time left on the maintenance timer and the maintenance to be performed when the timer expires. (default setpoint of 100 hours). If the timer is allowed to expire, the amber light on the Stacklights will begin to flash and the message center will indicate "Maintenance Due". When the maintenance screen is accessed, the system hourmeters will also be displayed. The maintenance required at the 500 hour, 1000 hour, 2000 hour and 3000 hour intervals will also be available by pressing the respective button on the maintenance screen. |
Last Five System FaultsPressing the "Faults" button on the System Values screen will display the last five system faults and the date and time at which they occurred. Pressing the fault # on the left of each fault code will display the fault message that would have appeared on the screen during the fault trip. While displaying the fault message, the current message center information will be displayed at the top of the page. |
Stack lights
The SNGII has a stack light mounted above its control panel. The individual lights in the stack will be illuminated in the following manner:
| Unit status | Stack light status |
| Unit not powered Unit Power, Control PLC Halted |
No Lights On |
| Unit Powered, Stop switch pressed System Off |
Green Light on Steady |
| System On Running or standby with system Full |
Amber Light On |
| System On Maintenance timer expired |
Amber light Flashing |
| System On, faulted | Red light flashing |
Message Center
During Operation, the line of text below the "Edit Setpoints" and "System Values" buttons on the Main Screen will display the current system status. While the unit is turned off, the message will simply indicate "SYSTEM OFF" however after the "Start" button has been pressed, the message center will indicate one of the following messages. In the event that the maintenance timer has expired, the standard message will be displayed however the "Maintenance Due: message will be flashed for a period of one second every 3 seconds. It should be noted that the message information will also be displayed on the top of other more commonly used display screens. The messages displayed are as follows:
| Event | Message |
|---|---|
| System Powered/ Stop Button Pressed | System: Off |
| System Powered/ Start Button Pressed Outlet pressure below setpoint unit about to start |
Caution: Unit Starting |
| System Powered/ Start Button Pressed Feed Air Compressor Running Only |
Pressurizing Membrane |
| Feed Air Compressor running, Booster inlet pressure > 75 psig Booster about to start |
Caution: Starting Booster |
| Booster running, Oxygen Content of product above Upper limit, High pressure vent valve Open |
Purging Booster |
| Booster running, Oxygen Content of produce below upper limit, High pressure vent valve closed |
Pumping Product |
| System has fully pressurized the outlet system and has shut down, will restart if outlet pressure falls below restart setpoint |
System Full |
| System has faulted | Faulted:Fault Code |
System faults.
During operation, the system monitors the following fault devices. When tripped, they will generate fault codes that will be displayed on the message center and will flash the fault light next to the display screen and the red stack Light a pre-set number of flashes. The flashes will consist of the fault light being turned on for a period of 1 second and then of for a period of one second until the last flash which will only flicker the light and then hold it off for a period of 3 second before re-starting.
| Fault | Input | Code | # of Flashes |
|---|---|---|---|
| Booster Low oil Pressure | X0 | low_oil | 2 |
| Booster High tempurature | X1 | hptemp | 3 |
| Booster Low inlet pressure | Analog | low_inlt | 4 |
| Booster High inlet pressure | Analog | highinlt | 4 |
| Feed air High temperature | X2 | Lp_temp | 5 |
| Membrane High inlet tempurature | Analog | mem_temp | 6 |
| Overrun timer trip | Runtimer | OVERRUN | 7 |
| Booster air circuit breaker | X4 | bstr_cbr | 8 |
| Feed air circuit breaker | X4 | feed_cbr | 8 |
When the system faults, in addition to the fault lights flashing, the interface screen will display a message elaborating the fault at hand and possible actions to prevent reocurrence. After the fault has been reset by pressing the Stop switch on the main screen the last five system faults can be displayed by pressing the "Faults" button on the system values screen. This button will display the Last Five Faults screen from which the operator can redisplay the messages. Click the fault code in the above table to see the message that would be displayed if the fault was redisplayed after the system was restarted. If the system was still faulted, the message center information at the top of the screen would still read "Faulted:faultcode".
** In order to prevent the unit running while an excessive leak has developed in the high pressure piping and distribution system, the control circuit is programmed to fault out if the setpoint pressure has not been reached within a pre-set period. The default setpoint is 8 hours runtime, resetable from the System setpoints screen.